Prices plus VAT plus shipping costs of 4,95 to GER (incl. VAT)
Delivery time 6 Workdays to NL, BE, AT (GER -1 workdays)
Quantity: |
- Order number: 809700-2101
Advantages
- We are ready to deliver: All information here
- Advice directly from experts
- Quality directly from the manufacturer
- Long-term stable temperature probes over years
- B2B customers welcome: All information here
Our employee will be happy to help you:
Julian Mäntele
Tel.: +49 (0)7653 96 59 771
E-Mail: jmaentele@testo-sensor.de
The APAQ R130 TC for thermocouples is a DIN rail transmitter for installation on standard DIN rails according to DIN EN50022. The sophisticated product design leaves sufficient space for mounting. It is optimally designed for use in plant and machine construction and is characterized by high accuracy, reliability, long-term stability and its robust product design. The transmitter is extremely insensitive to external influences such as vibration and EMC interference. Installation and commissioning are particularly user-friendly. For example, parameterization can be carried out wirelessly, conveniently and easily via the cell phone app using NFC technology. The monitoring functions such as sensor break monitoring, sensor short-circuit and measuring range monitoring can also be activated via this.
Here you can find our downloads for Hat rail transmitter for thermocouples APAQ-R130
Hat rail transmitter - Special features | ||||||||||||||||
Inputs and outputs | Input: thermocouples Output: 4 to 20mA, temperature linear output signal | |||||||||||||||
Accuracy & Long-term stability | Accuracy: depending on thermocouple Long-term stability: max drift of ±0.05°C or ±0.05% of span |year | |||||||||||||||
Design | Robust - vibration and shock resistant design Suitable for hat rails according to DIN EN50022 Compact housing design Facilitated mounting | |||||||||||||||
Parametrization | Configuration - wireless via NFC technology Free app for Iphone, Android & Huawei Parameterization templates for fast mass configuration Simple configuration with "copy and paste" in no time at all | |||||||||||||||
Alarm function | configurable via app Sensor break monitoring Sensor short circuit Measuring range monitoring | |||||||||||||||
Hat rail transmitter - Input Thermocouple | ||||||||||||||||
Measuring element | Material / Raw Material | Norm | Maximum configurable measuring range | Min. Span | Accuracy | |||||||||||
Type B | Pt30Rh-Pt6Rh | IEC 60584 | 0 °C to +1820 °C 32 °F to +3308 °F | +700 °C | +1292 °F | +100 °C to +400 °C: ±10 °C >400 °C: ±2 °C / 0,2% 1} | |||||||||||
Type E | NiCr-CuNi | IEC 60584 | -270 °C to +1000 °C -454 °F to +1832 °F | +50 °C | +122 °F | ±1 °C| ±0,2 % 1} | |||||||||||
Type J | Fe-CuNi | IEC 60584 | -210 °C to +1200 °C -346 °F to +2192 °F | +50 °C | +122 °F | ±1 °C| ±0,2 % 1} | |||||||||||
Type K | NiCr-Ni | IEC 60584 | -270 °C to +1300 °C -454 °F to +2372 °F | +50 °C | +122 °F | ±1 °C| ±0,2 % 1} | |||||||||||
Type N | NiCrSi-NiSi | IEC 60584 | -100 °C to +1300 °C -148 °F to +2372 °F | +100 °C | +212 °F | ±1 °C| ±0,2 % 1} | |||||||||||
Type N | NiCrSi-NiSi | IEC 60584 | -270 °C to -100 °C -418 °F to +148 °F | +100 °C | +212 °F | ±2 °C 1} | |||||||||||
Type R | Pt13Rh-Pt | IEC 60584 | -50 °C to +1750 °C -58 °F to +3182 °F | +300 °C | +572 °F | ±2 °C| ±0,2 % 1} | |||||||||||
Type S | Pt10Rh-Pt | IEC 60584 | -50 °C to +1750 °C -58 °F to +3182 °F | +300 °C | +572 °F | ±2 °C| ±0,2 % 1} | |||||||||||
Type T | Cu-CuNi | IEC 60584 | -270 °C to +400 °C -454 °F to +752 °F | +50 °C | +122 °F | ±2 °C| ±0,2 % 1} | |||||||||||
1} of span (cold junction compensation error is not included) | ||||||||||||||||
Input impedance | >10 MΩ | |||||||||||||||
Max. wire loop resistance | 5 kΩ | |||||||||||||||
Cold Junction Compensation | Internal or external | |||||||||||||||
Hat rail transmitter - General information about the input | ||||||||||||||||
Zero adjustment | Within measuring range | |||||||||||||||
Hat rail transmitter - Output | ||||||||||||||||
Output type | analog, temperature linear for TC | |||||||||||||||
Output signal (mA) | 4 to 20 | |||||||||||||||
Parametrization / Scaling | Configurable via NFC | |||||||||||||||
Load | 818 Ω at 24 VDC | |||||||||||||||
Connection type | 2-wire | |||||||||||||||
Hat rail transmitter - Time response | ||||||||||||||||
Closing time / Update time (Inor) | ~150 - 300 | |||||||||||||||
Heating period | After approx. 20 min. the typical accuracy is reached | |||||||||||||||
Signal attenuation / Ajustable output filtering (Inor) | 0,4 to 26 adjustable via App | |||||||||||||||
Measuring cycle | < 1 | |||||||||||||||
Hat rail transmitter - Sensor monitoring & sensor error | ||||||||||||||||
Sensor break / Short circuit | Upscale (≥21.0 mA) or Downscale (≤3.6 mA) | |||||||||||||||
Sensor failure effects (Inor) | according to NAMUR NE43 | |||||||||||||||
Hat rail transmitter - Accuracy and stability | ||||||||||||||||
Temperature influence | ||||||||||||||||
TC Type B, E, J, K, R, S, T | see table below | |||||||||||||||
TC Type N (-100...+1300 °C) | ±0,01 % < 4000 Ω 2} < ±0,02 % of span per °C | |||||||||||||||
TC Type N (-270...-100 °C) | ±0,01 % of span per °C | |||||||||||||||
Influence of the sensor cable | ||||||||||||||||
Thermocouples and Voltage | Negligible | |||||||||||||||
Further data | ||||||||||||||||
Supply voltage influence | <±0.005 % of span per volt | |||||||||||||||
Long-term drift | ±0.05 % of span per year | |||||||||||||||
Hat rail transmitter - Type | ||||||||||||||||
Dimensions | See drawing | |||||||||||||||
Material | Flammability | V0/HB, RoHS compliant | |||||||||||||||
Mounting | 35 mm hat rail according to DIN 50022 / EN 60715 | |||||||||||||||
Connection | Single wires, max. 1,5 mm², AWG 16 | |||||||||||||||
Weight | 40 | All dimensions in mm | ||||||||||||||
Hat rail transmitter - General data | ||||||||||||||||
Isolation | none | |||||||||||||||
Supply Voltage (VDC) | 8 to 32, polarity protected | |||||||||||||||
Hat rail transmitter - Ambient conditions | ||||||||||||||||
Ambient Temperatur | Storage: -40 °C to +85 °C | -40 °F to +185 °F Operating: -40 °C to +85 °C | -40 °F to +185 °F | |||||||||||||||
Humidity | 0 to 98 (non-condensing) | |||||||||||||||
Protection | Housing IP20 | Anschlussklemmen IP00 | |||||||||||||||
Vibration | according to IEC 60068-2-6, Test Fc, 10bis2000 Hz, 10 g | |||||||||||||||
Shock | according to IEC-60068-2-27, test Ea | |||||||||||||||
Environmental influences | according to IEC 60068-2-31:2008, Test Ec | |||||||||||||||
Hat rail transmitter - EMC | ||||||||||||||||
Standard | Directive: 2014/30/EU | Harmonized standards: EN 61326-1, EN 61326-2-3 | |||||||||||||||
Immunity performance | ESD, radiated EMC fields, magnetic fields: Criterion A Burst, conducted RF: Criteria A Overvoltage: standard deviation 1% of span | |||||||||||||||
Hat rail transmitter - Factory configuration (if not ordered otherwise) | ||||||||||||||||
Input | Pt100, 3-wire, 0 °C to 100 °C | |||||||||||||||
Output (mA) | 4 to 20 | |||||||||||||||
Sensor control | Upscale (≥21.0 mA) | |||||||||||||||
Hat rail transmitter - Mounting | ||||||||||||||||
You can easily mount the APAQ R130 hat rail transmitter on 35mm hat rails according to DIN EN50022. The mounting is easy because you can fix the transmitter on the rail without any tools. Mounting material for the installation of the transmitter is available as accessory. Important: To prevent measuring errors, the connecting screws for fastening the connecting cable must be tightened firmly. | ||||||||||||||||
Mounting and dismounting of the transmitter (1) Fix the upper part of the transmitter on the rail (2) Then press the lower part of the transmitter onto the rail. The electrical connection is made according to the wiring diagram (4) To remove the transmitter, use a screwdriver and bend the latch downwards | ||||||||||||||||
Hat rail transmitter - Configuration | Parametrization | ||||||||||||||||
Before making a configuration of APAQ C130TC you need to do following: Make sure that you have a mobile device with NFC communication activated. Download the app INOR Connect to your mobile device. Required versions: iOS: iOS 13 or later and Iphone 7 or later Android: Android 4.4 or later | Configuration procedure: Launch the app by clicking on the App icon or holding your mobile device against the transmitter on the part of the device where NFC is located (only possible with Android). Click on “Read Configuration” and hold your mobile device against the transmitter as explained in the first section. In the app you can edit the following: Sensor type and number of wire circuits Measuring range Upscale or Downscale sensor control TAG-number Password settings In the configuration window you can enter and change the parameters. The selected configuration is transferred to the transmitter by clicking the "Send to transmitter" button. After the transfer is completed, the transmitter uses the new parameters. |
Type: | Hat rail transmitter |
Output: | 4-20 mA |
Input: | Thermocouple |